Sample design for buffer tank and reheating output for LogoFresh fresh water units
Object designation:        
Date:        
Customer:        
Flamco / HFC Technical Consultant:        
         
Help to determine water consumption based on the type of object
Type of object/use
      Depending on the type and therefore the use of the object, there are different coefficients which influence the design/calculation.
           
Definition for single consumption
(specified single outlet capacity defined according to DIN 1988-300)
l/s   Σ - mixer taps for baths or showers (0.15l/s)
  l/s   Σ - mixer taps, washbasin, dishwasher (0.07l/s)
  l/s   Σ - kitchen sink (0.10l/s)
           
Total consumption as sum flow rate according to DIN 1988-300 l/s l/min Sum flow rate of all consumers according to DIN 1988-300
Total consumption as peak flow rate (DIN 1988-300) l/s l/min The peak flow rate reduces the sum flow rate when considering use-dependent concurrency of water draw-off (∑V˙R). Equation for the determination: VS = a(∑V˙R)b-c
           
Number of units       Caution: For cascading of LogoFresh unit´s optional cascading sets are required.
           
Basic and system parameters
Proposed value based on calculation peak.        
Required draw-off volume for a single unit. Fill in based on peak flow rate of the DIN 1988-300 or as a fixed value / directly entered value l/min     Performance definition of the entire single unit. Please choose the calculated performance specification due to the calculation peak (see above in yellow) or set up your own fixed value (e.g. 55 l/min.)
           
Please select using “Drag & Drop”
Selection of fresh water station with or without drinking water circulation (yes / no)
      Attention: For reasons of hygiene, we recommend always using fresh water stations with DHW circulations.
LogoFresh 100 and 120 are only available with circulations!
           
Theor. max. draw-off volume at 38°C mixed water temperature     l/min Theor. max. draw-off volume at a mixed water temperature of 38°C
Dropdown choose of the required hot water temperature
    °C Standard: 60 °C
Cold water temperature     °C Standard: 10 °C
Temperature difference, hot water tank     K Heat increase by _Kelvin
Buffer tank temperature     °C Buffer tank output temperature
Return line temperature     °C Standard Ø-value = 25°C
Further / other performance depending values please see techn. specifications in the output tables (return line temperatures may vary the volume flow for example, depending on the operating mode)
Buffer tank decrease     K Decrease by _Kelvin
           
System parameters          
Max draw-off volume     kW Unit’s mathematical max. draw-off volume
Critical draw-off duration     min Standard: 10 min
Heat source activation time     min Delay
Buffer tank recharging time     min Standard: 30 min
Cycle time     min Total duration
           
Energy requirements          
Energy requirements for crit. hot water tank     kWmin  
Buffer requirement until boiler start     kWmin  
Buffer requirement until hot water tank end     kWmin  
           
Reheating output           
Required reheating output     Kw Buffer tank
Freely available boiler output performance     % 100% with priority switching
Suggestion for boiler     kW Total
           
LogoFresh          
Suggestion for LogoFresh electronic type (CAUTION: CAN ONLY BE USED FOR THE HOT WATER OUTLET TEMPERATURES SPECIFIED ON THE RIGHT)   45 °C at the hot water outlet temperature of
    50 °C at the hot water outlet temperature of
    60 °C at the hot water outlet temperature of
           
Buffer tank          
Buffer tank suggestion     Litres  
Buffer tank type suggestion Article no.:    
           
           
Sample calculation! You have the responsibility to check the parameters.
For the buffer design, only the hot water proportion and the usage behaviour of standard residential building will be considered. If the building is used in a different way or system parameters change, the buffer tank and reheating output must be designed separately.
All designs without consideration for permanent consumers (t>15 min), draw-off points V_R> 0,5 l/s and circulation loss.