HANGER SPACING CALCULATOR
|
|
|
|
|
|
|
|
Symbol
|
Description
|
Equation
|
Source
|
Value
|
Units
|
|
|
|
|
|
|
|
|
|
|
Given/Assumed
|
|
|
|
|
|
|
|
|
|
|
|
-
|
Units
|
-
|
Given
|
I-P
|
-
|
|
|
D
|
|
-
|
Given
|
|
|
|
|
-
|
|
-
|
Given
|
|
-
|
|
|
-
|
Pipe Type
|
-
|
Given
|
|
-
|
|
|
WPIPE
|
Weight of Empty Pipe
|
-
|
Given
|
|
|
|
|
WWATER
|
Weight of Water
|
-
|
Given
|
|
|
|
|
WT
|
Total Weight
|
-
|
Given
|
|
|
|
|
T
|
Strength of Weakest Hanging
Element
|
-
|
Manufacturer's Product Data
|
|
lb
|
|
|
|
|
|
|
|
|
|
|
Hanger Spacing
|
|
|
|
|
|
|
|
|
|
|
|
SC
|
Maximum Calculated
Hanger Spacing
|
S = T-250 / 5 WT
|
NFPA 13 2019 17.1.2
|
|
ft
|
|
|
|
|
|
S13
|
Max. Permissible Spacing per
NFPA 13
|
-
|
NFPA 13 2019 Table 17.4.2.1
|
|
ft
|
|
|
SMAX
|
Maximum Permissible Hanger
Spacing
|
Minimum of SC & S13
|
NFPA 13 2019 Table 17.4.2.1
|
|
ft
|
|
|
|
|
|
|
|
|
|
|
References Used
|
|
|
|
|
|
|
|
|
|
|
|
1
|
NFPA 13
|
Standard for the
Installation of Fire Sprinkler Systems, 2019 Edition
|
|
|
|
|
|
|